Watts to Amps & Amps to Watts Calculator
Bidirectional Watts to Amps & Amps to Watts converter for DC, 120V/240V 1-phase, and 3-phase AC with 80% NEC limits.
Power & Current Inputs
DC · 1-PH · 3-PH- Real Power
- 1500.0 W (1.500 kW)
- Line Current
- 12.50 A
- Apparent (VA)
- 1500.0 VA
- NEC Continuous
- 15.63 A min breaker
Watts to Amps Quick-Reference Chart (12V DC, 24V DC, 120V AC, 240V AC)
Exact resistive currents (PF = 1.0) for common US appliances, solar batteries, and heating elements from 100 W to 5,000 W.
| Power (Watts) | 12V DC | 24V DC | 120V AC (1-Ph) | 240V AC (1-Ph) |
|---|---|---|---|---|
| 100 W | 8.33 A | 4.17 A | 0.83 A | 0.42 A |
| 300 W | 25.00 A | 12.50 A | 2.50 A | 1.25 A |
| 400 W | 33.33 A | 16.67 A | 3.33 A | 1.67 A |
| 500 W | 41.67 A | 20.83 A | 4.17 A | 2.08 A |
| 600 W | 50.00 A | 25.00 A | 5.00 A | 2.50 A |
| 1,000 W | 83.33 A | 41.67 A | 8.33 A | 4.17 A |
| 1,200 W | 100.00 A | 50.00 A | 10.00 A | 5.00 A |
| 1,500 W | 125.00 A | 62.50 A | 12.50 A | 6.25 A |
| 1,800 W | 150.00 A | 75.00 A | 15.00 A | 7.50 A |
| 2,000 W | 166.67 A | 83.33 A | 16.67 A | 8.33 A |
| 3,000 W | 250.00 A | 125.00 A | 25.00 A | 12.50 A |
| 4,500 W | 375.00 A | 187.50 A | 37.50 A | 18.75 A |
| 5,000 W | 416.67 A | 208.33 A | 41.67 A | 20.83 A |
Amps to Watts by Standard US Circuit Breaker (100% vs. NEC 80% Continuous)
NEC 210.20(A) limits continuous loads (running 3 hours or more) to 80% of standard overcurrent device rating unless the breaker is specifically listed for 100% continuous operation.
| Breaker Rating | 120V Max (100%) | 120V Cont. (80%) | 240V Max (100%) | 240V Cont. (80%) |
|---|---|---|---|---|
| 15 A Circuit | 1,800 W | 1,440 W | 3,600 W | 2,880 W |
| 20 A Circuit | 2,400 W | 1,920 W | 4,800 W | 3,840 W |
| 30 A Circuit | 3,600 W | 2,880 W | 7,200 W | 5,760 W |
| 40 A Circuit | 4,800 W | 3,840 W | 9,600 W | 7,680 W |
| 50 A Circuit | 6,000 W | 4,800 W | 12,000 W | 9,600 W |
| 60 A Circuit | 7,200 W | 5,760 W | 14,400 W | 11,520 W |
| 100 A Circuit | 12,000 W | 9,600 W | 24,000 W | 19,200 W |
Formulas & Power Factor Notes
Watts ↔ Amps Equations
DC: I = P / V | P = V × I
1-Ph AC: I = P / (V × PF) | P = V × I × PF
3-Ph AC: I = P / (√3 × V_LL × PF) | P = √3 × V_LL × I × PF
Limitations
- Watts vs. Volt-Amps (VA): Circuit breakers and wire ampacity respond to total current (VA), not just real watts. Always enter power factor < 1.0 for inductive motors, compressors, and fluorescent/LED drivers per NFPA 70 (NEC).
- Wire gauge & voltage drop: Once you know load amperes, size conductors in our NEC Wire Size Calculator and verify long-run line loss in the NEC Voltage Drop Calculator.
Field Questions & NEC Notes
How many amps is 1500 watts at 120 volts?
At 120V AC with unity power factor (PF = 1.0, resistive heat), 1500 watts draws exactly 12.50 amps (1500 ÷ 120 = 12.5 A). Because a 15A breaker is limited to 12A (1,440W) for continuous loads running 3 hours or longer, a 1500W space heater leaves minimal headroom for other devices on the same 15A branch circuit.
How many watts can a 15-amp or 20-amp 120V US breaker safely handle?
A 15A 120V circuit has a maximum trip ceiling of 1,800 W and an NEC 80% continuous limit of 1,440 W. A 20A 120V circuit has a 100% ceiling of 2,400 W and an 80% continuous limit of 1,920 W.
Why do 12V DC inverter amp calculations exceed Watts ÷ 12?
Pure DC load current is I = W ÷ 12 (so 1000W = 83.33 A at 12.0V). When powering a 120V AC load through a 12V battery inverter, include inverter efficiency (typically 85%–90%) and low-battery voltage sag (~10.5V–11.5V), which increases actual battery-side DC current to roughly 1000 ÷ (11.5 × 0.88) ≈ 99 A.