NFPA 70 · NEC Article 358 · Annex C Table C.1 LOCAL SOLVER · ZERO LOGIN

EMT Conduit Fill Chart (NEC Table C.1)

NEC 2026 Annex C Table C.1 EMT conduit fill chart with 3/4" EMT quick lookups for THHN, XHHW-2, and RHW-2.

3/4" EMT Quick Lookup (THHN / THWN-2 · ID 0.824" · 40% Area = 0.213 in²)

14 AWG THHN in 3/4" EMT
22 wires
15A lighting/branch
12 AWG THHN in 3/4" EMT
16 wires
20A receptacle circuits
10 AWG THHN in 3/4" EMT
10 wires
30A dryer / HVAC
8 AWG THHN in 3/4" EMT
6 wires
40A–50A circuits
6 AWG THHN in 3/4" EMT
4 wires
50A–60A EV / range
4 AWG THHN in 3/4" EMT
2 wires
31% 2-wire rule
NEC 2026 Annex C Table C.1 — EMT (Electrical Metallic Tubing) · THHN / THWN / THWN-2
Wire Size 1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG247121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG11134712192532
2/0 AWG01123610162026
3/0 AWG0111358131722
4/0 AWG0111247111418
250 kcmil001113691115
300 kcmil001113571013
350 kcmil00111246911
400 kcmil00011146810
500 kcmil0001113568

Practical EMT Field Limits Beyond Table C.1

Ampacity Bundling Ceiling (310.15(C)(1))

In commercial 120/208V homeruns using 12 AWG THHN (30A at 90°C), putting 9 current-carrying conductors in 3/4" EMT reduces ampacity to 30 A × 0.70 = 21 A—still legal for 20A breakers. Adding a 10th current-carrying wire drops the factor to 50% (15 A), disqualifying all 20A circuits in that pipe even though 16 wires physically fit under NFPA 70 Table C.1.

Mixed Gauges, Grounding & Voltage Drop

Table C.1 applies strictly to identical wires. If you are pulling three #6 hots plus a #10 ground in 3/4" EMT, use the NEC Mixed-Wire Conduit Fill Calculator to compute exact square-inch fill and jam ratio, and verify steel-conduit AC inductive reactance drop in our NEC Voltage Drop Calculator.

Field Questions & NEC Notes

How many 12 AWG THHN wires fit in 3/4-inch EMT under NEC 2026?

Per NEC Annex C Table C.1, 3/4" EMT holds up to 16 conductors of 12 AWG THHN/THWN-2 (0.533 in² × 40% = 0.2132 in²; 0.2132 ÷ 0.0133 = 16.03). Keep in mind that if more than 3 of those wires carry current simultaneously, NEC Table 310.15(C)(1) bundling derating reduces 12 AWG THHN ampacity (for 10–20 current-carrying conductors, 30A × 50% = 15A, which is no longer valid for a 20A breaker).

Can steel EMT serve as the equipment grounding conductor (EGC) to save one wire?

Yes, in most non-healthcare installations. Under NEC 250.118(4), properly coupled steel EMT qualifies as an equipment grounding conductor. However, many project specifications, health care patient care areas (NEC 517.13), and inspectors still require an insulated green copper EGC—if pulled, that green wire counts toward Table C.1 fill.

How many 6 AWG THHN wires fit in 3/4-inch EMT for a 60A EV charger?

3/4" EMT holds up to 4 conductors of 6 AWG THHN (4 × 0.0507 = 0.2028 in² ≤ 0.2132 in² at 40% fill). A typical 240V hardwired EV charger needs only two #6 hots plus one #10 ground (0.1225 in², or 23.0% fill), making 3/4" EMT an easy, code-compliant pull.