NEC Voltage Drop Calculator
US NEC 2026 voltage drop calculator using Chapter 9 Tables 8 & 9 impedance for 1-phase, 3-phase, and DC runs.
Circuit Parameters
PRESETS M1–M4- Voltage at Load
- 235.30 V
- Impedance (Zeff)
- 0.4900 Ω/kft
- Resistance (R)
- 0.4900 Ω/kft
- Reactance (XL)
- 0.0510 Ω/kft
Copper vs. Aluminum · Side-by-Side NEC Compliant Comparison
- Exact Drop
- 4.70 V (1.96%)
- Delivered V
- 235.30 V
- Est. Material / 100 ft
- $260–$350
- Exact Drop
- 4.90 V (2.04%)
- Delivered V
- 235.10 V
- Est. Material / 100 ft
- $128–$184
Saved Circuit Schedule & Multi-Run Comparison
0 / 6 RUNS SAVEDNo circuits logged yet. Click + Save Run above to compare up to 6 branch circuits or feeders side-by-side, export a CSV schedule, or print an NEC field sheet.
| Circuit Label | System & Load | 1-Way Run | Conductor | Drop (V / %) | Load V | NEC Status | Actions |
|---|
Worked NEC 2026 Voltage Drop Examples
Pre-calculated using NEC Chapter 9 Table 9 AC resistance and reactance at 75°C. Use these field benchmarks to sanity-check branch circuits and feeders before pulling wire.
| Circuit Scenario | System | Load | 1-Way Run | Conductor | Drop (V) | Drop (%) | NEC Status | Min ≤3% |
|---|---|---|---|---|---|---|---|---|
| Garage 20A Branch (120V) | 120V 1-Ph | 16 A | 100 ft | 12 AWG Cu | 6.40 V | 5.33% | >5% | 8 AWG |
| 48A EV Charger (240V) | 240V 1-Ph | 48 A | 100 ft | 6 AWG Cu | 4.70 V | 1.96% | PASS ≤3% | 6 AWG |
| Detached Shop 100A Subpanel | 240V 1-Ph | 80 A | 150 ft | 1 AWG Al | 6.04 V | 2.52% | PASS ≤3% | 1 AWG |
| Well Pump 240V (250 ft) | 240V 1-Ph | 15 A | 250 ft | 10 AWG Cu | 7.85 V | 3.27% | 3–5% | 8 AWG |
| Commercial 208V 3-Ph Feeder | 208V 3-Ph | 100 A | 200 ft | 1/0 AWG Cu | 4.54 V | 2.18% | PASS ≤3% | 1 AWG |
| Industrial 480V 3-Ph Motor | 480V 3-Ph | 65 A | 300 ft | 4 AWG Cu | 9.97 V | 2.08% | PASS ≤3% | 4 AWG |
NEC Chapter 9 Formula & Engineering Scope
1-Phase / DC & 3-Phase Equations
V_drop (1-Ph / DC) = (2 × L × I × Z_eff) / (1000 × N)
V_drop (3-Ph) = (√3 × L × I × Z_eff) / (1000 × N)
Z_eff = R_ac × cos(θ) + X_L × sin(θ)
Where L is one-way length in feet, I is load amperes, N is parallel sets per phase, and R_ac, X_L come directly from NFPA 70 (NEC) Chapter 9 Table 9 (75°C base with Table 8 Note 2 temperature adjustment).
Limitations & When Not to Rely on This Estimate Alone
- Ampacity is checked separately: Meeting 3% voltage drop does not guarantee Table 310.16 ampacity compliance—verify both in our NEC Wire Size Calculator.
- Motor starting inrush: Steady-state FLA is used here; large motors with locked-rotor currents (6× FLA) require dedicated starting voltage dip checks.
- NEC 250.122(B) EGC upsizing: When you upsize phase conductors for voltage drop, remember to proportionally upsize the equipment ground.
- Energy code & workplace rules: Commercial building feeders must also satisfy state energy codes tracked by the US DOE Building Energy Codes Program (ASHRAE 90.1 / Title 24) and OSHA 29 CFR 1910.303 workplace electrical standards.
Field Questions & NEC Notes
Why does NEC Chapter 9 Table 9 give a different drop than the simple 2KIL/CM formula?
The older 2 × K × I × L / CM shortcut uses a fixed DC resistivity constant (K ≈ 12.9 for copper) and ignores AC skin effect, steel conduit eddy losses, and inductive reactance (XL). For conductors 1/0 AWG and larger—especially inside steel EMT or RMC—reactance adds substantial voltage drop that Table 9 captures via Zeff = R cos θ + XL sin θ.
Are the NEC 3% branch and 5% total voltage drop limits mandatory?
In NEC 210.19(A) Informational Note No. 3 and NEC 215.2(A)(2) Informational Note No. 2, the 3% branch / 5% combined limits are informational recommendations rather than mandatory code text—except where specifically mandated (such as NEC 647.4(D) sensitive electronic equipment at 1.5%/2.5%, NEC 695.7 fire pumps at 15% starting / 5% running, or state energy codes like California Title 24 and ASHRAE 90.1).
If I upsize ungrounded conductors for voltage drop, must I upsize the equipment grounding conductor (EGC)?
Yes. Per NEC 250.122(B), whenever ungrounded phase conductors are increased in circular mil area for voltage drop, the equipment grounding conductor must be increased proportionately according to the circular mil ratio of the installed phase conductor to the minimum code-required phase conductor.
Should I enter one-way distance or total wire length?
Enter the one-way circuit run length from the panelboard or transformer to the load. The calculator automatically multiplies by 2 for single-phase and DC circuits (accounting for out-and-back return current) and by √3 (1.732) for balanced three-phase circuits.