3-Phase Power Calculator (kW, kVA & Amps)
3-phase power calculator for US 208V, 240V, 480V, and 600V systems solving kW, kVA, kVAR, amps, and shaft HP.
3-Phase System Inputs
PRESETS M1–M4P = √3 × 480.0 V × 60.00 A × 0.85 ÷ 1000 = 42.40 kW
- Real Power (P)
- 42.40 kW
- Apparent (S)
- 49.88 kVA
- Reactive (Q)
- 26.28 kVAR
- Line Current
- 60.00 A
- Wye Voltages
- 480.0V / 277.1V
- Shaft HP
- 52.31 HP (θ 31.8°)
208V vs. 480V 3-Phase Line Current Reference Table (5–200 kW)
Compare line current on standard US 208V commercial and 480V industrial 3-phase systems at both 0.85 inductive motor power factor and 1.0 resistive power factor.
| Real Power | kVA (@ 0.85 PF) | 208V (0.85 PF) | 208V (1.0 PF) | 480V (0.85 PF) | 480V (1.0 PF) |
|---|---|---|---|---|---|
| 5 kW | 5.9 kVA | 16.3 A | 13.9 A | 7.1 A | 6.0 A |
| 10 kW | 11.8 kVA | 32.7 A | 27.8 A | 14.2 A | 12.0 A |
| 15 kW | 17.6 kVA | 49.0 A | 41.6 A | 21.2 A | 18.0 A |
| 25 kW | 29.4 kVA | 81.6 A | 69.4 A | 35.4 A | 30.1 A |
| 50 kW | 58.8 kVA | 163.3 A | 138.8 A | 70.8 A | 60.1 A |
| 75 kW | 88.2 kVA | 244.9 A | 208.2 A | 106.1 A | 90.2 A |
| 100 kW | 117.6 kVA | 326.6 A | 277.6 A | 141.5 A | 120.3 A |
| 150 kW | 176.5 kVA | 489.8 A | 416.4 A | 212.3 A | 180.4 A |
| 200 kW | 235.3 kVA | 653.1 A | 555.1 A | 283.0 A | 240.6 A |
3-Phase Equations & Balanced-Load Assumptions
Standard 3-Phase Identities
S (kVA) = (√3 × V_LL × I_line) / 1000
P (kW) = S × PF = (√3 × V_LL × I_line × PF) / 1000
Q (kVAR)= √(S² − P²) | V_LL = √3 × V_LN
Once line current is solved, verify 3-phase feeder drop in our NEC Voltage Drop Calculator (using the √3 steel/PVC impedance model) and size conductors in the NEC Wire Size Calculator.
Scope Limitations
- Balanced loads assumed: Unbalanced single-phase loads tapped off a 3-phase Wye panel require per-phase current analysis and neutral sizing per NFPA 70 (NEC) §220.61.
- Non-linear harmonic loads: VFDs, UPS rectifiers, and LED lighting introduce total harmonic distortion (THD) that lowers true power factor below displacement cos θ; also verify motor efficiency standards via the US DOE Electric Motors guidance.
Field Questions & NEC Notes
Why does the 3-phase power formula multiply by √3 (1.732) instead of 3?
Total 3-phase power equals 3 × VLN × Iphase × PF. In a balanced Wye system, line-to-line voltage is VLL = √3 × VLN, so substituting VLN = VLL / √3 reduces 3 / √3 to exactly √3 (1.73205). The same √3 × VLL × Iline identity holds for balanced Delta loads.
What is the difference between kW, kVA, and kVAR in a 3-phase system?
kW (Real Power) performs actual mechanical or heating work. kVA (Apparent Power) determines conductor and transformer current loading (kVA = kW ÷ PF). kVAR (Reactive Power) sustains magnetic fields in motors and transformers (kVAR = √(kVA² − kW²)).
Should I enter 277V or 480V on a US 480Y/277V commercial panel?
Select Line-to-Line (VLL) and enter 480 V (or select Line-to-Neutral and enter 277 V—the calculator automatically computes the matching 480.0 V line-to-line voltage using √3).